Winter Maintenance for Diesel Generator Sets

Nov. 19, 2026

I. Engine Fuel

In winter, low temperatures increase the viscosity of diesel fuel and reduce its fluidity, which hinders proper atomization and combustion. This can degrade both the power output and fuel efficiency of the diesel engine. Therefore, it is essential to use light diesel fuel with a low pour point and good ignition characteristics. As a general rule, the pour point of the diesel fuel should be 7–10°C lower than the lowest local ambient temperature for the season.

II. Starting with the Aid of an Open Flame

In regions with extremely low temperatures, an open flame may be used to assist in starting the engine; however, the air filter must never be removed. A common (though risky) method involves soaking cotton waste in diesel, igniting it, and placing it inside the intake manifold. Doing this allows unfiltered, dust-laden air to be drawn directly into the cylinders, causing abnormal wear on components such as pistons and cylinder walls. Furthermore, it can lead to rough engine operation and mechanical damage.

III. Draining Cooling Water (Prematurely or Not at All)

Before shutting down the generator, allow it to run at idle until the cooling water temperature drops below 60°C (to the point where it is no longer hot to the touch) before stopping the engine and draining the water. Draining the cooling water too early—while the engine block is still hot—can cause the metal to contract rapidly when exposed to cold air, potentially leading to cracks. When draining, ensure all residual water is completely removed from the engine block to prevent it from freezing, expanding, and cracking the block. It is highly recommended to use antifreeze regardless of the season; this is especially important for high-end generator sets, as antifreeze serves not only as a coolant but also as a protective agent for the diesel engine.

IV. Selection of Lubricating Oil

In winter, use engine oil with a low pour point. To facilitate starting, the oil temperature can be raised by warming the engine externally—for instance, by using a water bath method. The use of an open flame is not recommended, as it can cause the engine oil in the oil pan to deteriorate or even char. This reduces or completely destroys the oil's lubricating properties, thereby accelerating mechanical wear.

V. Starting Procedures

In winter, if conditions permit, it is best to install a water-jacket heater on the generator set. This maintains a certain "body temperature" for the engine, ensuring it can be started easily at any time. Some operators, seeking a quick start, may resort to an improper method: starting the engine without coolant and adding it only afterward. This practice causes severe damage to the equipment and is strictly prohibited. The correct preheating procedure is as follows: cover the radiator with an insulating blanket, open the drain valve, and continuously pour clean, soft water (heated to 60–70°C) into the radiator. Once the water flowing out of the drain valve feels hot to the touch, close the valve and proceed to start the engine.

VI. Precautions for Operating Under Load in Low Temperatures

After a diesel generator set has started, some operators may be too eager to apply a load immediately. When a diesel engine has just started, its internal temperature is low and the engine oil is highly viscous; consequently, the oil cannot easily reach the moving friction surfaces, which leads to significant mechanical wear. Furthermore, components such as plunger springs, valve springs, and injector springs are susceptible to "cold brittleness" and may easily fracture. Therefore, after starting a diesel generator in winter, allow it to idle at a low-to-medium speed for several minutes. Only once the coolant temperature has reached 60°C should the unit be put under load.